Twin Short — 20 ft standard DC block

Two DC blocks joined end-to-end on their blind short sides with the PCS & MV skid along the long side

Overview

Two DC blocks joined end-to-end on their blind short sides. Cable ends face outward, and the skid sits along the long side below the pair.

PCS & MV skid
Twin Short — end-to-end pair with skid below
ParameterValue
DC blocks2 × 20 ft (short pair)
PCS & MV skids1 × 40 ft @2h · 20 ft @4h
Section size12.3 × 8.4 m (40.4 × 27.5 ft)

Energy capacity

Section energy and power rating for this configuration.

DC blockBESS section (2 blocks)Duration
6.25 MWh12.5 MWh / 6.25 MW2h
6.25 MWh12.5 MWh / 3.125 MW4h

Clearance and spacing defaults

Service clearance and spacing used by default. All values are adjustable in BESSLayout.

SettingDefault
DC block door side3.5 m (11.5 ft)
DC block cable end2 m (6.6 ft)
PCS & MV skid3 m (9.8 ft) all sides
Fire separation (between DC blocks of different sections)5 m (16.4 ft)

Cable layout

Each DC block cables from its outward-facing cable end down to the skid below. At 40 ft the skid has two PCS sections — one per block.

Single BESS section footprint

Land area at default clearance. Door clearance above, skid clearance below, cable-end clearance on each side.

Cable ends facing outward

Skid below the DC pair, doors facing up

186 m²(1,998 ft²)
16.3 × 11.4 m
53.5 × 37.3 ft
Land useValue
Footprint16.3 × 11.4 m (53.5 × 37.3 ft)
Total area186 m² (1,998 ft²)

Multiple BESS sections footprint

Land area for four sections, in a row and in a 2 × 2 grid, at the default spacing.

Clearance
4 × 1 grid

4 sections · 8 DC blocks

777 m²(8,359 ft²)
68.3 × 11.4 m
224.0 × 37.3 ft
2 × 2 grid

4 sections · 8 DC blocks

765 m²(8,236 ft²)
33.6 × 22.8 m
110.3 × 74.6 ft