Twin Short Centered — 20 ft standard DC block

Four DC blocks in two end-to-end pairs sharing a single central PCS & MV skid — the most compact twin arrangement

Overview

Four standard DC blocks in two pairs, each in a twin configuration, with a PCS & MV skid (20 ft or 40 ft) centered between them.

PCS & MV skid
Twin Short Centered — doors facing the shared skid aisle
ParameterValue
DC blocks4 × 20 ft
PCS & MV skids1 × 20 ft / 40 ft
Section size12.3 × 14.3 m (40.4 × 47.0 ft)

Energy capacity

Section energy and power rating for this configuration.

DC blockBESS section (4 blocks)Duration
6.25 MWh25 MWh / 6.25 MW4h

Clearance and spacing defaults

Service clearance and spacing used by default. All values are adjustable in BESSLayout.

SettingDefault
DC block door side3.5 m (11.5 ft)
DC block cable end2 m (6.6 ft)
PCS & MV skid3 m (9.8 ft) all sides
DC block stacking gap0.2 m (0.7 ft)
Fire separation (between DC blocks of different sections)5 m (16.4 ft)

Cable layout

DC cables run from the outward-facing end of each DC block to the central PCS & MV skid.

Single BESS section footprint

Land area at default clearance. When DC block doors face the skid, their service zones overlap — reducing total footprint.

Shared clearance

DC block service doors facing the skid

262 m²(2,822 ft²)
18.3 × 14.3 m
60.1 × 47.0 ft
Separate clearance

DC block service doors facing outward

372 m²(4,005 ft²)
18.3 × 20.3 m
60.1 × 66.6 ft
Land useSharedSeparate
Footprint18.3 × 14.3 m (60.1 × 47.0 ft)18.3 × 20.3 m (60.1 × 66.6 ft)
Total area262 m² (2,822 ft²)372 m² (4,005 ft²)

Multiple BESS sections footprint

Land area for four sections, in a row and in a 2 × 2 grid, at the default spacing.

Clearance
4 × 1 grid

4 sections · 16 DC blocks

920 m²(9,901 ft²)
64.3 × 14.3 m
210.8 × 47.0 ft
2 × 2 grid

4 sections · 16 DC blocks

996 m²(10,726 ft²)
29.6 × 33.6 m
97.2 × 110.3 ft