Solo Centered — 20 ft standard DC block

Two standalone DC blocks on either side of one centered PCS & MV skid — one skid feeds both blocks for the shortest cable run

Overview

Two standalone DC blocks on either side of one centered PCS & MV skid. Each block's cable end faces the skid for a short cable run, but unlike a twin the blocks never touch each other.

PCS & MV skid
Solo Centered — one skid between two standalone blocks
ParameterValue
DC blocks2 × 20 ft (standalone)
PCS & MV skids1 × 40 ft @2h · 20 ft @4h
Section height14.3 m (47.0 ft)

Energy capacity

Section energy and power rating for this configuration.

DC blockBESS section (2 blocks)Duration
6.25 MWh12.5 MWh / 6.25 MW2h
6.25 MWh12.5 MWh / 3.125 MW4h

Clearance and spacing defaults

Service clearance and spacing used by default. All values are adjustable in BESSLayout.

SettingDefault
DC block door side3.5 m (11.5 ft)
DC block cable end2 m (6.6 ft)
PCS & MV skid3 m (9.8 ft) all sides
Fire separation (between DC blocks of different sections)5 m (16.4 ft)

Cable layout

Each DC block cables to its own PCS section on the shared skid. At 40 ft the skid has two sections — one per block — so cable runs are short on both sides.

Single BESS section footprint

Land area at default clearance. Door clearance on both long sides, skid clearance at each end.

Doors facing outward

Skid clearance covers the cable-end zone at each end

388 m²(4,174 ft²)
18.2 × 21.3 m
59.7 × 69.9 ft
Land useValue
Footprint18.2 × 21.3 m (59.7 × 69.9 ft)
Total area388 m² (4,174 ft²)

Multiple BESS sections footprint

Land area for four sections, in a row and in a 2 × 2 grid, at the default spacing.

Clearance
4 × 1 grid

4 sections · 8 DC blocks

1359 m²(14,630 ft²)
63.8 × 21.3 m
209.2 × 69.9 ft
2 × 2 grid

4 sections · 8 DC blocks

1356 m²(14,599 ft²)
33.4 × 40.6 m