Solo Vertical — 20 ft standard DC block
A single DC block standing vertically with the PCS & MV skid alongside the blind long side — a narrower section for thin strips
Overview
A single DC block standing vertically, with the PCS & MV skid alongside the blind long side. The narrower section width fits thin strips the standard solo cannot.
| Parameter | Value |
|---|---|
| DC blocks | 1 × 20 ft (vertical) |
| PCS & MV skids | 1 × 20 ft |
| Section size | 8.4 × 6.1 m (27.5 × 19.9 ft) |
Energy capacity
Section energy and power rating for this configuration.
| DC block | BESS section (1 block) | Duration |
|---|---|---|
| 6.25 MWh | 6.25 MWh / 3.125 MW | 2h |
| 6.25 MWh | 6.25 MWh / 1.5625 MW | 4h |
Clearance and spacing defaults
Service clearance and spacing used by default. All values are adjustable in BESSLayout.
| Setting | Default |
|---|---|
| DC block door side | 3.5 m (11.5 ft) |
| DC block cable end | 2 m (6.6 ft) |
| PCS & MV skid | 3 m (9.8 ft) all sides |
| Fire separation (between DC blocks of different sections) | 5 m (16.4 ft) |
Cable layout
The DC cable runs from the block's cable end to the adjacent PCS & MV skid.
Single BESS section footprint
Land area at default clearance. Skid clearance on one side, door clearance on the other, cable clearance above.
Skid and door clearance zones on opposite sides
37.3 × 39.6 ft
| Land use | Value |
|---|---|
| Footprint | 11.4 × 12.1 m (37.3 × 39.6 ft) |
| Total area | 137 m² (1,477 ft²) |
Multiple BESS sections footprint
Land area for four sections, in a row and in a 2 × 2 grid, at the default spacing.
4 sections · 4 DC blocks
149.3 × 39.6 ft
4 sections · 4 DC blocks
74.6 × 75.8 ft