Quad — 20 ft standard DC block
Four DC blocks in a 2×2 cluster with one PCS & MV skid — the densest single section
Overview
Four DC blocks arranged in a 2×2 cluster with one PCS & MV skid below.
| Parameter | Value |
|---|---|
| DC blocks | 4 × 20 ft (2×2 cluster) |
| PCS & MV skid | 1 × 40 ft |
| Section width | 12.3 m (40.4 ft) |
Energy capacity
At 2h the four blocks exceed a single skid’s conversion capacity, so the solver automatically uses Quad Split with two skids instead.
| DC block | BESS section (4 blocks) | Duration |
|---|---|---|
| 6.25 MWh | 25 MWh / 6.25 MW | 4h |
Clearance and spacing defaults
Service clearance and spacing used by default. All values are adjustable in BESSLayout.
| Setting | Default |
|---|---|
| DC block door side | 3.5 m (11.5 ft) |
| DC block cable end | 2 m (6.6 ft) |
| PCS & MV skid | 3 m (9.8 ft) all sides |
| Fire separation (between DC blocks of different sections) | 5 m (16.4 ft) |
Cable layout
All four DC blocks cable down to the single PCS & MV skid. At 40 ft the skid has two PCS sections — each section serves one column.
Single BESS section footprint
Land area at default clearance. Door clearance above, skid clearance below, cable-end clearance on each side.
Skid below the 2×2 cluster, top-row doors facing up
53.5 × 57.5 ft
| Land use | Value |
|---|---|
| Footprint | 16.3 × 17.5 m (53.5 × 57.5 ft) |
| Total area | 286 m² (3,076 ft²) |
Multiple BESS sections footprint
Land area for four sections, in a row and in a 2 × 2 grid, at the default spacing.
4 sections · 16 DC blocks
224.0 × 57.5 ft
4 sections · 16 DC blocks
110.3 × 103.4 ft