Quad Split — 20 ft standard DC block

A skid on each DC row of the 2×2 cluster — the 2h-capable Quad with two skids

Overview

A 2×2 DC cluster with a skid above the top row and another below the bottom row. Each skid serves two blocks.

PCS & MV skid
Quad Split — skid above and below the 2×2 cluster
ParameterValue
DC blocks4 × 20 ft (2×2 cluster)
PCS & MV skids2 × 40 ft @2h · 20 ft @4h
Section width12.3 m (40.4 ft)

Energy capacity

Section energy and power rating for this configuration.

DC blockBESS section (4 blocks)Duration
6.25 MWh25 MWh / 12.5 MW2h
6.25 MWh25 MWh / 6.25 MW4h

Clearance and spacing defaults

Service clearance and spacing used by default. All values are adjustable in BESSLayout.

SettingDefault
DC block door side3.5 m (11.5 ft)
DC block cable end2 m (6.6 ft)
PCS & MV skid3 m (9.8 ft) all sides
Fire separation (between DC blocks of different sections)5 m (16.4 ft)

Cable layout

Each skid serves the two DC blocks in its adjacent row. At 40 ft each skid has two PCS sections — one per block.

Single BESS section footprint

Land area at default clearance. Skid clearance above and below, cable-end clearance on each side.

Skids above and below

One skid per DC row, doors facing inward

374 m²(4,031 ft²)
16.3 × 23.0 m
53.5 × 75.3 ft
Land useValue
Footprint16.3 × 23.0 m (53.5 × 75.3 ft)
Total area374 m² (4,031 ft²)

Multiple BESS sections footprint

Land area for four sections, in a row and in a 2 × 2 grid, at the default spacing.

Clearance
4 × 1 grid

4 sections · 16 DC blocks

1567 m²(16,865 ft²)
68.3 × 23.0 m
224.0 × 75.3 ft
2 × 2 grid

4 sections · 16 DC blocks

1443 m²(15,532 ft²)
33.6 × 42.9 m
110.3 × 140.8 ft